MonitorIQ MIQ-IO24F PLC Brand Independent
24-Channel Fused PLC I/O Interface Module
The MIQ-IO24F is a 24-channel industrial PLC I/O interface module designed to provide individual fused protection and visual status indication for 24 VDC digital control circuits.
Each channel includes a replaceable 1 A ATO/ATC blade fuse and dedicated LED status indication. The module is arranged as two 12-channel banks and supports both independent-bank and common-source PLC output configurations.
The MIQ-IO24F combines channel protection, source protection, status indication, organized terminal wiring, and DIN-rail mounting in one assembly.
PLC Brand Independent
Designed for standard 24 VDC discrete I/O applications and not tied to a specific PLC manufacturer. The MIQ-IO12F and MIQ-IO24F can be integrated with a wide range of industrial controllers and output modules where the electrical interface requirements are compatible.
- 24Channels
- 24 VDCNominal
- 1 APer-channel fuse
- DINTH35 / TH15 / G32
See the listing for current pricing and availability. Free shipping on eBay orders. Distributor availability coming soon. For OEM and volume pricing, contact sales.
Technical data
MIQ-IO24F key specifications
| Nominal operating voltage | 24 VDC |
|---|---|
| Number of channels | 24 |
| Channel arrangement | Two 12-channel banks |
| Channel fuse | 1 A, 32 VDC ATO/ATC |
| Independent-bank source protection | 2 A per bank |
| Common-source configuration | 4 A active source fuse; second source fuse omitted |
| Channel indication | Individual LED per channel |
| Bank indication | Power/source LED per bank |
| Signal type | Digital / discrete |
| PLC compatibility | Brand-independent for compatible 24 VDC PLC discrete I/O systems |
| PCB construction | 1.6 mm, 2-layer FR-4 |
| Mounting | DIN rail |
| DIN-rail compatibility | EN 60715 TH35, TH15, G32 |
| Approx. footprint | 158 mm along DIN rail × 124 mm across rail |
| Approx. installed height | 46.6 mm above DIN-rail mounting surface (TH35-7.5) |
| PCB size | 155 mm × 108 mm |
| Installation type | Open-type industrial control component |
| I/O wire size | 16–24 AWG |
| I/O strip length | 8 mm |
| Common/GND wire size | 18–24 AWG |
| Common/GND strip length | 8 mm |
Full dimensions are shown in the dimensional drawing on the Downloads page. Finished product weight: to be published.
Interactive
MIQ-IO24F 3D model
Drag to rotate, scroll or pinch to zoom, right-click or two-finger drag to pan. Shown mounted in its DIN-rail carrier on a 35 mm (TH35) DIN rail.
Wiring options
Operating configurations
Independent-bank operation
Each 12-channel bank receives its own 24 VDC source. Typical configuration uses one 2 A source fuse per bank with J5 removed.
- Bank A source fuse
- 2 A
- Bank B source fuse
- 2 A
- J5 jumper
- Removed
Common-source operation
A single protected source may be used with a 24-channel sourcing PLC output module. In this configuration, the active source uses a 4 A fuse, the second source fuse is omitted, and J5 provides Bank B power indication.
- Active source fuse
- 4 A
- Second source fuse
- Omitted
- J5 jumper
- Installed (Bank B indication)
Use cases
Typical applications
- PLC digital outputs
- Relay coils
- Indicators
- Solenoids
- Contactor-interface circuits
- Machine controls
- Industrial automation systems
- OEM control panels
- Test equipment
- Retrofit control systems
Package contents
- 1 × MIQ-IO24F interface module
- 1 × DIN-rail mounting carrier
- All required channel and source fuses
Why MonitorIQ
Shared product benefits
Protect PLC I/O investment
Individual replaceable fuses provide localized protection for field circuits instead of relying solely on upstream protection or expensive PLC hardware.
Faster troubleshooting
Dedicated status LEDs allow technicians to quickly identify active control circuits.
Organized panel wiring
Fuse protection, indication, source protection, and field terminals are consolidated into a single DIN-rail assembly.
Standard replacement fuses
Uses widely available full-size ATO/ATC blade fuses.
Designed for industrial controls
Purpose-built for 24 VDC PLC discrete I/O applications rather than general-purpose DC distribution.
Documentation
MIQ-IO24F documents
-
MIQ-IO24F Product datasheetPDF · Rev. 0 · 2 pagesDownload
-
MIQ-IO24F Installation & Configuration GuidePDF · Draft Rev. 1 · Includes wiring and J5 configuration · Covers both modelsDownload
-
MIQ-IO24F Mechanical / dimensional drawingPDF · Rev. 0 · A3, 1:1 · Top, front and side viewsDownload
-
MIQ-IO24F 3D CAD model (STEP)STEP AP214 in ZIP · 5.0 MB · PCB assembly, without DIN-rail carrierDownload
Installation & Compliance
The MIQ-IO12F and MIQ-IO24F are open-type industrial control components intended for installation inside a suitable electrical control enclosure by qualified personnel.
The complete MonitorIQ assemblies are not currently UL Listed or UL Recognized. Individual components may carry independent UL Listing, UL Recognition, UL94 material ratings, or other manufacturer approvals where applicable. Component-level approvals do not constitute certification of the complete assembly.